H3CA-8 Omron Timer
| Rated supply voltage | 100/110/120 VAC (50/60 Hz) | 
|---|---|
| Operating voltage range | 85 to 110% of rated supply voltage | 
| Power consumption | Approx. 10 VA/Approx. 1 W | 
| Time ranges(Number of ranges) | 7 | 
| Time ranges | 0.1 to 99.9 s 1 to 999 s 0.1 to 99.9 min 1 to 999 min 0.1 to 99.9 h 1 to 999 h 10 to 9990 h  | 
| Input method | No-voltage input (open and short-circuit) | 
| Output modes | A: Power ON delay | 
| Control output (Contact output) | Time-limit contact: DPDT Resistive load: 3 A at 250 VAC Minimum applicable load: 10 mA at 5 VDC (failure level: P Reference value)  | 
| Reset system | Self-reset | 
| Power reset | Reset time: 0.1 s max. | 
| Display method | LCD 3 digit | 
| Ambient temperature (Operating) | -10 to 55℃ (with no icing) | 
| Ambient humidity (Operating) | 35 to 85% | 
| Accuracy of operating time | ±0.3% ±0.05 s (The values are based on the set value.) | 
| Setting error | ±0.5% ±0.05 s (The values are based on the set value.) | 
| Influence of voltage | ±0.3% ±0.05 s (The values are based on the set value.) | 
| Influence of temperature | ±0.3% ±0.05 s (The values are based on the set value.) | 
| Insulation resistance | 100 MΩ min. (at 500 VDC) | 
| Dielectric strength | Between current carrying metal parts and non-current carrying metal parts: 2000 VAC 50/60 Hz 1 min Between control output terminals and operating circuit: 2000 VAC 50/60 Hz 1 min Between non-continuous contacts: 1000 VAC 50/60 Hz 1 min  | 
| Impulse withstand voltage | Between power terminals: 3 kV Between current carrying terminals and exposed non-current carrying metal parts: 4.5 kV  | 
| Vibration resistance | Destruction: 10 to 55 Hz, 0.75 mm single amplitude each in 3 directions for 1 hour Malfunction: 10 to 55 Hz, 0.5 mm single amplitude each in 3 directions for 10 min  | 
| Shock resistance | Destruction: 1,000 m/s**2, 3 times each in 6 directions Malfunction: 100 m/s**2, 3 times each in 6 directions  | 
| Life expectancy | Electrical: 100,000 operations min. (3 A at 250 VAC resistive load at 1800 operations/h) Mechanical: 10 million operations min. (under no load at 1,800 operations/h)  | 
| Degree of protection | IP40 | 
| Mounting method | Flush mounting / Surface mounting | 
| External connection method | 8-pin round socket | 
| Applicable socket | P2CF-08, P2CF-08-E, P3G-08, PL08 | 
| Accessory (sold separately) | Soft Cover: Y92A-48D Hard Cover: Y92A-48B Flush mounting adapter: Y92F-30/Y92F-70/Y92F-71  | 
									





	

Reviews